Cables · BS 7671

Voltage Drop Calculator

Enter the cable mV/A/m, the design current and the run length to get the voltage drop in volts and as a percentage of the supply, checked against the usual limits.

Last reviewed

Voltage drop -V
% of supply
-
Limit
-
-

How voltage drop is calculated

Voltage drop along a cable is worked out from its tabulated millivolt-per-amp-per-metre figure, the current the circuit is designed to carry, and how far the cable runs:

Vd (V) = (mV/A/m × Ib × L) ÷ 1000

The result is then expressed as a percentage of the nominal supply voltage. For single-phase work use the single-phase mV/A/m value; for three-phase, use the three-phase value from the cable table, which already accounts for line voltage.

The limits

BS 7671 recommends that voltage drop from the origin of the installation to the load stays within about 3% for lighting and 5% for other uses on a 230 V supply. Those percentages are measured from the origin, so on a longer installation you need to account for drop in the submains as well as the final circuit.

About the presets

The dropdown holds commonly quoted mV/A/m figures for 70°C thermoplastic insulated copper conductors, rounded for convenience. They are there to save time, not to replace the table. For anything you are going to certify, read the exact value for your conductor size and installation method straight from BS 7671.

Common questions

What is the maximum allowed voltage drop in the UK?
BS 7671 recommends voltage drop does not exceed 3% for lighting and 5% for other circuits on a 230 V supply, measured from the origin of the installation to the point of use.
Do I use the single-phase or three-phase mV/A/m value?
Match it to the circuit. Single-phase circuits use the single-phase (two-core) figure; three-phase circuits use the three-phase figure from the table, which is lower because it relates to line voltage.
Does this include the resistance and reactance of larger cables?
The tabulated mV/A/m value already combines the relevant components for the conductor size. For larger cables where reactance matters, the table gives separate r, x and z columns; enter the z value here for the closest result.
For guidance only. This tool gives an indicative voltage drop to support design. It is not a substitute for a full design by a competent person to the current edition of BS 7671. Verify all mV/A/m values against the published cable tables.