Maximum Demand Calculator

Enter the connected load for each type of circuit in a dwelling and the tool applies the usual On-Site Guide diversity allowances to give an assessed maximum demand.

Last reviewed

Assessed max demand -A
Apparent power
-
Connected (no diversity)
-
Suggested main switch
-

How diversity is applied

Adding up every connected load gives a figure far higher than an installation ever draws, because the loads do not all peak together. The On-Site Guide gives allowances for each type of circuit in a single dwelling, and this tool applies them like this:

Lighting 66% · Sockets: largest + 40% of the rest · Cooker: 10 A + 30% above 10 A (+5 A socket)
Showers: largest + 25% of the rest · Water heating, heating, EV, other: 100%

Each load is converted to a current at 230 V, the allowance is applied, and the results are added to give the assessed maximum demand. That current then sets the supply, the main switch and the tails.

Where the figures come from

These are the single-household allowances from the IET On-Site Guide. Other premises, blocks of flats and three-phase supplies use different tables, and modern loads such as EV charging and heat pumps are often taken at full load unless a load-management scheme is in place.

Common questions

Is this for a single house?
Yes. The allowances used here are the single-dwelling figures. Flats, commercial premises and three-phase supplies follow different diversity tables.
Why is there no diversity on the EV charger?
A charge point can draw its full rating for hours, so it is normally taken at 100%. Where a load-management or dynamic-control system limits it, a lower figure can be justified.
Does it size the cable and main switch?
It gives the assessed demand in amps and suggests the next standard main-switch rating. The final cable and device selection still needs the full design checks.
For guidance only. Diversity is a matter of engineering judgement. These are the standard single-dwelling allowances applied mechanically; confirm the assessment against the IET On-Site Guide and BS 7671 for the actual installation.