Lighting · Lumen method

Lighting Lux Calculator

Estimate how many luminaires a room needs to reach a target illuminance, using the lumen method with utilisation and maintenance factors.

Last reviewed

Luminaires needed -
Exact (unrounded)
-
Achieved lux with that number
-
Typical layout
-

Indicative only. Assumes a square room with an even grid and half-spacing to the walls. A real layout follows the fitting's spacing-to-mounting-height ratio and the actual room shape.

The lumen method

The lumen method gives the average illuminance a space will reach for a given number of fittings, or the number of fittings needed to hit a target:

N = (E × A) ÷ (F × UF × MF)

where N is the number of luminaires, E is the target lux, A is the area in m², F is the lumen output per luminaire, UF is the utilisation factor and MF is the maintenance factor. The calculator rounds up, then shows the average lux you would actually achieve with that whole number of fittings.

About the factors

The utilisation factor depends on the room proportions and how reflective the ceiling, walls and floor are, and comes from the luminaire manufacturer's photometric data. The maintenance factor allows for dirt and lamp depreciation over the maintenance cycle. The defaults here are sensible starting points, not a substitute for the real figures for your fitting and space.

Common questions

What lux level should I design to?
It depends on the task and the space. Circulation might be 100 to 150 lux, a general office 300 to 500 lux, fine detail work more. Use the value from the relevant lighting standard or guidance for the application.
Where do I get the utilisation factor?
From the luminaire's photometric data, against the room index and the surface reflectances. The single default here is only a rough placeholder.
Does this give a uniform layout?
No. The lumen method gives an average across the working plane. Spacing and uniformity still need to be checked, ideally with a proper lighting layout.
For guidance only. The lumen method gives an average illuminance for a first pass. It does not check uniformity, glare or emergency lighting. Use manufacturer photometric data and the relevant lighting standards for the final design.