Conduit & Trunking Fill Calculator
Add up your cables and get the smallest conduit or trunking that stays within the space factor, with the fill percentage for the size it suggests.
Last reviewed
The space factor method
The quick way to size containment is the space factor: the combined cross-sectional area of the cables should not exceed a set fraction of the inside of the conduit or trunking.
The usual maxima are about 40% for conduit and 45% for trunking. Each cable is counted by its overall diameter, insulation included, not the conductor size. This tool sums the cables you enter and returns the smallest standard size that stays within the factor.
Assumed cable diameters
The presets use typical overall diameters for single-core 70°C thermoplastic (6491X) conductors: 1.0 mm² at 2.9 mm through to 25 mm² at 9.7 mm. Real diameters vary a little by manufacturer, so check the data sheet for a tight design.
When to use the unit method instead
The space factor is a first pass. For conduit runs with bends, or longer than about three metres, the IET On-Site Guide sets out a unit or factor method using cable factors and conduit factors that allow for the run length and the number of bends. Use that for anything you are going to certify.