Protection · BS 7671

Maximum Zs Calculator

Work out the highest earth fault loop impedance a protective device will allow and still disconnect in time, then check a measured Zs against the temperature-corrected limit.

Last reviewed

Maximum Zs -Ω
Disconnection current Ia
-
0.8 rule-of-thumb limit
-

How maximum Zs is worked out

For the fault loop to disconnect in the required time, the earth fault loop impedance has to be low enough to drive the current that operates the protective device. For a breaker that means reaching its instantaneous magnetic trip:

Zsmax = (Cmin × U0) ÷ Ia = (0.95 × 230) ÷ Ia

where U0 is the nominal line voltage to earth (230 V), Cmin is the 0.95 voltage factor, and Ia is the current that causes disconnection in the required time. For a BS EN 60898 breaker (and the equivalent BS EN 61009 RCBO) that current is a fixed multiple of the rating:

Type B: Ia = 5 × In · Type C: Ia = 10 × In · Type D: Ia = 20 × In

The 0.8 rule of thumb

The tabulated maxima assume the conductors are at their normal operating temperature. When you test, the installation is usually colder, so its resistance is lower than it will be in service. A widely used rule of thumb is to compare the measured value against 0.8 of the tabulated maximum, which builds in the temperature rise. BS 7671 also gives the more precise 0.95 correction approach in its tables.

MCCBs

A moulded-case circuit breaker to BS EN 60947-2 trips instantaneously at its magnetic setting Im, which is usually adjustable rather than fixed like a Type B, C or D. Choose MCCB, enter the rating and the instantaneous trip as a multiple of In from the device data, commonly around 10, and the maximum Zs follows the same equation.

Fuses and other devices

For fuses (BS 88, BS 3036, BS 1362 and similar) the disconnection current is not a simple multiple of the rating, it is read from the device's time/current curve for the 0.4 s or 5 s disconnection time. Read Ia off that curve and enter it under “Custom” to get the maximum Zs. The device standard sets which table applies, see the BS numbers reference.

Common questions

What is the maximum Zs for a Type B MCB?
It is 218.5 divided by five times the rating. For a 32 A Type B that is about 1.37 Ω before temperature correction, or roughly 1.09 Ω against the 0.8 rule of thumb.
Do RCBOs use the same figures?
Yes for the overcurrent side. A BS EN 61009 RCBO trips on overcurrent to the same B, C or D characteristic as the equivalent breaker, so the maximum Zs is the same. Its residual current protection is separate.
How do I do it for an MCCB?
Choose the MCCB option, enter the rating and the instantaneous magnetic trip as a multiple of the rated current from the device data (often adjustable, commonly around 10). The maximum Zs is then 218.5 divided by that trip current.
Should I use 230 V or the measured voltage?
The tabulated maxima use the nominal 230 V with the 0.95 factor. Working from a measured supply voltage is possible but the standard values, and this calculator, use the nominal figure.
For guidance only. This gives indicative maximum Zs values for verification. Confirm the device characteristic, the disconnection time required and the correct table against the current edition of BS 7671 and the device data before relying on a result.